director 2/64 installation guide
director 2/64 installation guide 2–61
Installing and Configuring the Director 2/64
NOTE: Rebooting the HAFM server does not adversely effect the operation of the director
or fabric.
5. Verify that call-home event notification is enabled through the HAFM server.
a. In the Products or Fabrics View page, choose Maintenance > Configure
Call Home Event. The HAFM Configure Call Home Event notification
dialog box displays.
If a check mark displays in the check box, call home is enabled. If a check
mark does not display in the check box, click the box to add a check mark.
6. Enable Call-Home Notification for each director:
a. In the Hardware View page, choose Maintenance > Configure Call Home
Event Notification to place a check mark in the check box to enable the Call
Home Event Notification.
b. Repeat step a for each director.
7. See “Test Remote Notification” on page 2–61 for instructions on testing the
call-home feature.
Test Remote Notification
If the e-mail and one of the call-home notification features are enabled, set up the
HAFM application to test these remote notification features. Because the features are
configured at the HAFM application, call-home and e-mail notification are enabled for
multiple directors.
NOTE: Prior to using test remote notification, complete the steps in the previous sections,
“Configure and Enable E-mail Notification” and either:
• Configure the Call-Home via Dial-out Feature, or
• Configure and Enable the Proactive Services Call-Home via LAN Feature.
Use these steps to test remote notification:
1. Close the Hardware View page for the director by clicking Close at the
Navigation Control panel.
2. Choose Maintenance > Test Remote Notification. The Test Remote
Notification dialog box displays, as shown in Figure 2–39.