director 2/64 service manual

director 2/64 service manual 2–75
Diagnostics
21
At the director, inspect the amber LED at the top of each CTP2 card.
Is the amber LED illuminated on both CTP2 cards?
NO YES
Failure of both CTP2 cards is indicated. Go to step 7.
Analysis for an Ethernet link failure is not described in this MAP. Go to MAP 0000:
Start MAP on page 2–12. If this is the second time at this step, contact the next level of
support. Exit MAP.
22
Inspect fan module operational states at the Embedded Web Server interface.
1. At the View panel, click the FRU Properties tab. The View panel (FRU
Properties tab) displays.
2. Inspect the Status fields for both fan modules.
Does the Status field display a Failed message for either fan module?
NO YES
A fan module failure is indicated. Go to step 5.
23
Inspect CTP2 card operational states at the Embedded Web Server interface. Inspect
the Status fields for both CTP2 cards.
Does the Status field display a Failed message for either CTP2 card?
NO YES
A CTP2 card failure is indicated. Go to step 7.
24
Inspect SBAR assembly operational states at the Embedded Web Server interface.
Inspect the Status fields for both assemblies.