director 2/64 service manual

director 2/64 service manual 2–85
Diagnostics
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
20
The director is configured for Open Fabric mode but the switch or director at the other
end of the ISL is not configured to Open Fabric mode.
The director is configured for S/390 mode but the switch or director at the other end of
the ISL is not configured to S/390 mode.
Configure the director operating mode:
1. Ensure the director is set offline (Set Offline State on page 3–44).
2. At the Hardware View for the selected director, choose Configure > Operating
Parameters > Switch Parameters. The Configure Switch Parameters dialog
box displays.
3. Select the operating mode as follows:
Choose the Open Systems option to set the director to open systems
operating mode, then choose Open Fabric 1.0 from the Interop Mode list
box.
Choose the S/390 option to set the director to S/390 operating mode.
4. Click Activate to save the selection and close the window.
Did configuring the operating mode solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
21
A loopback plug is connected to the port and there is no diagnostic test running. Is a
loopback plug in the port receptacle?
YES NO
Contact the next level of support. Exit MAP.