director 2/64 service manual

2–10 director 2/64 service manual
Diagnostics
585 Primitive sequence timeout. Go to MAP 0600: UPM Card
Failure and Link Incident
Analysis.
586 Invalid primitive sequence
received for current link state.
Go to MAP 0600: UPM Card
Failure and Link Incident
Analysis.
600 SBAR assembly hot-insertion
initiated.
No action required.
601 SBAR assembly recognized. No action required.
602 SBAR assembly anomaly
detected.
No action required.
603 SBAR assembly hot-removal
completed.
No action required.
604 SBAR assembly failure. Go to MAP 0500: FRU Failure
Analysis.
605 SBAR assembly revision not
supported.
Go to MAP 0500: FRU Failure
Analysis.
607 Director contains no
operational SBAR assemblies.
Go to MAP 0500: FRU Failure
Analysis.
608 User initiated SBAR
switch-over.
No action required.
800 High temperature warning
(UPM card thermal sensor).
Go to MAP 0600: UPM Card
Failure and Link Incident
Analysis.
801 Critically hot temperature
warning (UPM card thermal
sensor).
Go to MAP 0600: UPM Card
Failure and Link Incident
Analysis.
802 UPM card shutdown due to
thermal violation.
Go to MAP 0600: UPM Card
Failure and Link Incident
Analysis.
805 High temperature warning
(SBAR assembly thermal
sensor).
Go to MAP 0500: FRU Failure
Analysis.
Table 2–3: Event Codes Versus Maintenance Action (Continued)
Event
Code Explanation Action