Is the amber LED illuminated on both CTP2 cards?
NO YES
↓ Failure of both CTP2 cards is indicated. Event codes are not recorded. Go to
MAP 0500: FRU Failure Analysis on page 2–68. Exit MAP.
10
A director-to-HAFM server Ethernet link failure is indicated.
Go to step 23 to obtain event codes. If no event codes are found, go to MAP 0400:
Loss of Console Communication on page 2–55.
Exit MAP.
11
Does a red diamond with yellow background (failure indicator) display as the
background to the icon representing the director reporting the problem?
YES NO
↓ Go to step 14.
12
Double-click the icon representing the director reporting the problem. The Hardware
View displays. At the Hardware View:
• Observe the director Status table is yellow and the director status is NOT
OPERATIONAL.
• Inspect FRUs for a blinking red and yellow diamond (failed FRU indicator) that
overlays the FRU graphic.
Do blinking red and yellow diamonds overlay all UPM card graphics?
NO YES
↓ Failure of all installed UPM cards is indicated. Go to step 23 to obtain event
codes. If no event codes are found, go to MAP 0600: UPM Card Failure and
Link Incident Analysis on page 2–76. Exit MAP.
13
Blinking red and yellow diamonds overlay both serial crossbar (SBAR) assembly
graphics or both fan module graphics.