Diagnostics
Is the amber LED illuminated on both CTP2 cards?
NO YES
Failure of both CTP2 cards is indicated. Event codes are not recorded. Go to
MAP 0500: FRU Failure Analysis on page 2–68. Exit MAP.
10
A director-to-HAFM server Ethernet link failure is indicated.
Go to step 23 to obtain event codes. If no event codes are found, go to MAP 0400:
Loss of Console Communication on page 2–55.
Exit MAP.
11
Does a red diamond with yellow background (failure indicator) display as the
background to the icon representing the director reporting the problem?
YES NO
Go to step 14.
12
Double-click the icon representing the director reporting the problem. The Hardware
View displays. At the Hardware View:
Observe the director Status table is yellow and the director status is NOT
OPERATIONAL.
Inspect FRUs for a blinking red and yellow diamond (failed FRU indicator) that
overlays the FRU graphic.
Do blinking red and yellow diamonds overlay all UPM card graphics?
NO YES
Failure of all installed UPM cards is indicated. Go to step 23 to obtain event
codes. If no event codes are found, go to MAP 0600: UPM Card Failure and
Link Incident Analysis on page 2–76. Exit MAP.
13
Blinking red and yellow diamonds overlay both serial crossbar (SBAR) assembly
graphics or both fan module graphics.