director 2/64 service manual
2–18 director 2/64 service manual
Diagnostics
A FRU failure is indicated. Go to step 23 to obtain event codes. If no event codes are
found, go to MAP 0500: FRU Failure Analysis on page 2–68. Exit MAP.
18
A green circle displays as the background to the icon representing the director
reporting the problem. Although the director is operational, a minor problem may
exist.
Double-click the icon representing the director reporting the problem. The Hardware
View displays. At the Hardware View:
• Inspect CTP2 cards, SBAR assemblies, and fan modules for a yellow triangle that
overlays the FRU graphic and indicates FRU beaconing is enabled.
• Inspect UPM cards for a yellow triangle (attention indicator) that overlays the
UPM card graphic.
Does a yellow triangle overlay a CTP2 card, SBAR assembly, or fan module graphic?
YES NO
↓ Go to step 20.
19
Beaconing is enabled for the FRU.
1. Consult the customer and next level of support to determine the reason FRU
beaconing is enabled.
2. Disable FRU beaconing.
a. At the Hardware View, right-click the FRU graphic. A menu displays.
b. Click Enable Beaconing. The check mark disappears from the box adjacent
to the option, and FRU beaconing is disabled.
Was FRU beaconing enabled because a FRU failure or degradation was suspected?
YES NO
↓ The director is operational. Exit MAP.
Go to step 22.