director 2/64 service manual
director 2/64 service manual 2–25
Diagnostics
34
Is the amber LED on a CTP2 card, SBAR assembly, or fan module illuminated?
NO YES
↓ A FRU failure is indicated. Go to step 23 to obtain event codes. If no event
codes are found, go to MAP 0500: FRU Failure Analysis on page 2–68. Exit
MAP.
35
Is the green PWR OK LED on a power supply extinguished?
NO YES
↓ A power supply failure is indicated. Go to step 23 to obtain event codes. If no
event codes are found, go to MAP 0100: Power Distribution Analysis on page
2–34. Exit MAP.
The director is operational. Exit MAP.
36
Are you at a PC with a web browser (such as Netscape Navigator or Microsoft Internet
Explorer) and an Internet connection to the director reporting the problem?
YES NO
↓ Go to step 53.
37
Is the web browser PC powered on and communicating with the director through the
Internet connection?
NO YES
↓ Go to step 39.
38
Boot the web browser PC.
1. Power on the PC in accordance with the instructions delivered with the PC. The
Windows desktop displays.