Is the amber LED on a CTP2 card, SBAR assembly, or fan module illuminated?
NO YES
A FRU failure is indicated. Go to step 23 to obtain event codes. If no event
codes are found, go to MAP 0500: FRU Failure Analysis on page 2–68. Exit
MAP.
35
Is the green PWR OK LED on a power supply extinguished?
NO YES
A power supply failure is indicated. Go to step 23 to obtain event codes. If no
event codes are found, go to MAP 0100: Power Distribution Analysis on page
2–34. Exit MAP.
The director is operational. Exit MAP.
36
Are you at a PC with a web browser (such as Netscape Navigator or Microsoft Internet
Explorer) and an Internet connection to the director reporting the problem?
YES NO
Go to step 53.
37
Is the web browser PC powered on and communicating with the director through the
Internet connection?
NO YES
Go to step 39.
38
Boot the web browser PC.
1. Power on the PC in accordance with the instructions delivered with the PC. The
Windows desktop displays.