director 2/64 service manual
2–34 director 2/64 service manual
Diagnostics
54
The link incident record provides the attached director port number(s) and one or more
of the following event codes and messages. Record all event codes that may relate to
the reported problem.
581 - Link interface incident - implicit incident.
582 - Link interface incident - bit-error threshold exceeded.
583 - Link failure - loss of signal or loss of synchronization.
584 - Link failure - not-operational primitive sequence (NOS) received.
585 - Link failure - primitive sequence timeout.
586 - Link failure - invalid primitive sequence received for the current link state.
Were one or more event codes found?
YES NO
↓ Perform director fault isolation at the HAFM server (or customer-supplied
server).
Go to step 3.
Go to Table 2–3 on page 2-2.
MAP 0100: Power Distribution Analysis
This MAP describes fault isolation for the director power distribution system,
including defective AC power cords, redundant power supplies, or the power module
assembly.
1
Was an event code 200, 201, 202, or 208 observed at the Director 2/64 Event Log
(HAFM server) or at the Embedded Web Server event log?
YES NO
↓ Go to step 10.
2
Table 2–4 lists event codes, brief explanations of the codes, and the associated steps
that describe fault isolation procedures.