director 2/64 service manual

2–36 director 2/64 service manual
Diagnostics
The director is operational. Exit MAP.
5
Ensure the indicated power supply is correctly installed and seated in the director. If
required, partially remove and reseat the power supply.
Was a corrective action performed?
YES NO
Go to step 7.
6
Verify redundant power supply operation.
1. Inspect the power supply and ensure the green PWR OK LED illuminates and all
amber LEDs extinguish.
2. At the HAFM server’s Hardware View, observe the graphic representing the
power supply and ensure a failure symbol (blinking red and yellow diamond) does
not display.
Is a failure indicated?
YES NO
The director is operational. Exit MAP.
7
A redundant power supply failed and must be removed and replaced (RRP: Redundant
Power Supply on page 4–17).
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and replacement.
Did power supply replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.