director 2/64 service manual

2–40 director 2/64 service manual
Diagnostics
The director is operational. Exit MAP.
17
Both power supplies failed and must be removed and replaced (RRP: Redundant
Power Supply on page 4–17). Perform the data collection procedure as part of FRU
removal and replacement.
Did dual power supply replacement solve the problem?
NO YES
The director is operational. Exit MAP.
A dual power supply failure is not confirmed. Replace both original power supplies to
avoid the cost of expending replacement FRUs. Continue.
18
A power module assembly failure is indicated and must be removed and replaced
(RRP: Power Module Assembly on page 4–26). This procedure is non concurrent and
must be performed while director power is off.
Did power module assembly replacement solve the problem?
NO YES
The director is operational. Exit MAP.
A power module assembly failure is not confirmed. Replace the original power
module assembly to avoid the cost of expending a replacement FRU. Continue.
19
One or both power supplies are operational, but logic cards are not receiving DC
power. In-card circuit breakers for all logic cards may have tripped due to a power
surge, or the backplane failed.
Power cycle the director to reset all logic cards (Power-On Procedure on page 3–40).
Did power cycling the director solve the problem?
NO YES
The director is operational. Exit MAP.