director 2/64 service manual

director 2/64 service manual 2–41
Diagnostics
20
The backplane failed and must be removed and replaced (RRP: Backplane on page
4–29).
This procedure is nonconcurrent and must be performed while director power is
off.
Perform the data collection procedure as part of FRU removal and replacement.
Did backplane replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
21
Is fault isolation being performed at the HAFM server?
YES NO
Fault isolation is being performed at the Embedded Web Server interface. Go
to step 25.
22
At the HAFM server’s Hardware View, does a yellow triangle display at the alert
panel and a blinking red and yellow diamond (failed FRU indicator) display over a
power supply graphic?
NO YES
A redundant power supply failed. Go to step 7.
23
At the HAFM server’s Hardware View, does a gray square display at the alert panel,
a No Link status displays at the director Status table, and graphical FRUs are
uninstalled?
YES NO
A green circle displays at the alert panel and the director is operational. Exit
MAP.