director 2/64 service manual

2–46 director 2/64 service manual
Diagnostics
5
The backplane failed POSTs (indicated by a 01 FRU code) and must be removed and
replaced (RRP: Backplane on page 4–29).
This procedure is nonconcurrent and must be performed while director power is
off.
Perform the data collection procedure as part of FRU removal and replacement.
Did backplane replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
6
A CTP2 card failed POSTs (indicated by a 02 FRU code) and must be removed and
replaced (RRP: Redundant CTP2 Card on page 4–5).
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and replacement.
Did CTP2 card replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
7
An SBAR assembly failed POSTs (indicated by a 03 FRU code) and must be removed
and replaced (RRP: Redundant SBAR Assembly on page 4–20).
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and replacement.
Did SBAR assembly replacement solve the problem?
NO YES
The director is operational. Exit MAP.