director 2/64 service manual
director 2/64 service manual 2–47
Diagnostics
Contact the next level of support. Exit MAP.
8
A fan module failed POSTs (indicated by a 05 FRU code) and must be removed and
replaced (RRP: Redundant Fan Module on page 4–23).
• This procedure is concurrent and can be performed while director power is on.
• Perform the data collection procedure as part of FRU removal and replacement.
Did fan module replacement solve the problem?
NO YES
↓ The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
9
A power supply failed POSTs (indicated by a 06 FRU code) and must be removed and
replaced (RRP: Redundant Power Supply on page 4–17).
• This procedure is concurrent and can be performed while director power is on.
• Perform the data collection procedure as part of FRU removal and replacement.
Did power supply replacement solve the problem?
NO YES
↓ The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
10
A UPM card failed POSTs (indicated by a 08 through 0F FRU code) and must be
removed and replaced (RRP: UPM Card on page 4–9).
• This procedure is concurrent and can be performed while director power is on.
• Perform the data collection procedure as part of FRU removal and replacement.
Did UPM card replacement solve the problem?
NO YES
↓ The director is operational. Exit MAP.