director 2/64 service manual

director 2/64 service manual 2–47
Diagnostics
Contact the next level of support. Exit MAP.
8
A fan module failed POSTs (indicated by a 05 FRU code) and must be removed and
replaced (RRP: Redundant Fan Module on page 4–23).
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and replacement.
Did fan module replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
9
A power supply failed POSTs (indicated by a 06 FRU code) and must be removed and
replaced (RRP: Redundant Power Supply on page 4–17).
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and replacement.
Did power supply replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
10
A UPM card failed POSTs (indicated by a 08 through 0F FRU code) and must be
removed and replaced (RRP: UPM Card on page 4–9).
This procedure is concurrent and can be performed while director power is on.
Perform the data collection procedure as part of FRU removal and replacement.
Did UPM card replacement solve the problem?
NO YES
The director is operational. Exit MAP.