FW 07.00.00/HAFM SW 08.06.00 HP StorageWorks Director 2/64 Installation Guide (AA-RSNGE-TE/958-000289-003, March 2005)
Director 2/64 installation guide 41
9. Connect the equipment rack power cords to separate (for redundancy) facility power sources,
providing single-phase, 120 to 240 VAC current.
Figure 15 AC power connections
HP system/e and industry-standard 19-inch rack installation
To install the director in a HP system/e or industry-standard 19-in rack, complete the procedures in
the following sections:
• Install the anti-tip feet on an HP system/e rack, page 41
• Install mounting bracket hardware in the rack, page 42
• Prepare the front and rear rack columns, page 45
• Prepare the switch for installation, page 47
• Finalize the rack-mounting procedure, page 48
• Sliding shelf installation—for an HAFM appliance only, page 50
• Recommended cable management, page 53
Install the anti-tip feet on an HP system/e rack
Use the following procedure to mount anti-tip feet on a HP system/e rack only (Figure 16):
1. Place the anti-tip feet (1), provided in the HP system/e and industry-standard 19-in rack-mount
kits on the front and rear of the rack base.
2. Secure the anti-tip feet (1) to the base of the rack (front and rear).