FW 07.00.00/HAFM SW 08.06.00 HP StorageWorks Director 2/64 Installation Guide (AA-RSNGE-TE/958-000289-003, March 2005)

Installing and configuring the director42
3. Lower the rack feet (2) until they touch the floor.
Figure 16 Mounting anti-tip feet for a HP system/e rack
Install mounting bracket hardware in the rack
Use these steps to install the mounting hardware in a rack.
NOTE: The nine Us used to mount the switch are called U1 through U9; U1 is the lowest of the
nine Us. Note also that one U below the switch is required for the rail tray for a total of 10Us to
mount the switch.
1. Determine the appropriate placement for the switch inside the rack. It is important to consider
the number of switches you intend to install.
2. Determine the mounting location for the rail tray (Figure 17).
NOTE: The rail tray will be mounted 1U below the switch. Because the switch should be mounted
no higher than U11, the tray should be mounted no higher than U10. Make sure there are at least
2Us above the top of the switch empty for the sliding shelf.