FW 07.00.00/HAFM SW 08.06.00 HP StorageWorks Director 2/64 Installation Guide (AA-RSNGE-TE/958-000289-003, March 2005)

Installing and configuring the director48
4. Repeat step 2 and step 3 for the second front mounting bracket.
Figure 23 Installing the rack-mounting brackets on the switch
5. Locate the two rear mounting brackets in the shipping carton.
6. Position a rear mounting bracket (3) so that the bracket’s center holes (1) line up with the 1st
and 3rd threaded holes on the back portion of the switch side.
NOTE: The slotted end (2) of the bracket should face toward the back of the switch.
7. Secure the rear mounting bracket to the switch using two 10-32, flat-head Phillips screws.
8. Repeat step 6 and step 7 for the second rear mounting bracket.
Finalize the rack-mounting procedure
Use the following sections to complete the installation procedure.
WARNING! The director weighs approximately 115 pounds. Use proper handling and lifting
equipment to reduce the possibility of injury or product damage.