FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)
3
MAP 0000: Start MAP
3-27
Maintenance Analysis Procedures (MAPS)
39
Does the SANpilot interface appear operational with the View panel
displayed?
NO YES
↓ Go to step 44.
40
A Page cannot be found, Unable to locate the server, HTTP 404 -
file not found, or other similar message appears. The message
indicates the web browser PC cannot communicate with the director
because:
• The director-to-PC Internet link could not be established.
• AC power distribution in the director failed, or AC power was
disconnected.
• Both of the director CTP2 cards failed.
Continue.
41
Ensure the director reporting the problem is connected to facility AC
power and the power switch (circuit breaker) at the rear of the director
is set to the ON (up) position. Inspect the director for indications of
being powered on:
• At the front bezel, an illuminated power LED (green) or system
error LED (amber).
• An illuminated green LED on the active CTP2 card, and
illuminated green PWR OK LEDs on both power supplies.
• Audio emanations and airflow from cooling fans.
Does the director appear powered on?
YES NO
↓ A power distribution problem is indicated. Go to MAP 0100:
Power Distribution Analysis on page 3-34. Exit MAP.