FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)
3
3-32
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
Does the State field display a Failed message for any of the FRUs?
YES NO
↓ The director appears operational. Exit MAP.
A FRU failure is indicated. Continue to the next step to obtain event
codes. If no event codes are found, go to MAP 0500: FRU Failure
Analysis on page 3-75. Exit MAP.
52
Obtain event codes from the SANpilot event log.
NOTE: If multiple event codes are found, note all codes and associated
severity levels. Record the date, time, and sequence, and determine if the
codes are related to the problem. Begin fault isolation with the most recent
event code with the highest severity level. Other codes may accompany this
event code, or may indicate a normal indication after a problem is recovered.
a. At the View panel, select Monitor at the left side of the panel.
The Monitor panel opens with the Port List page displayed.
b. At the Monitor panel, click the Log tab. The Monitor panel (Log
tab) displays (Figure 3-12).
c. Record the event code, date, time, and severity (Informational,
Minor, Major, or Severe).
d. Record all event codes that may relate to the reported problem.