FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)
3
3-34
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
54
The link incident record provides the attached director port numbers
and one or more of the following event codes and messages. Record
all event codes that may relate to the reported problem.
581 - Link interface incident - implicit incident.
582 - Link interface incident - bit-error threshold exceeded.
583 - Link failure - loss of signal or loss of synchronization.
584 - Link failure - not-operational primitive sequence (NOS)
received.
585 - Link failure - primitive sequence timeout.
586 - Link failure - invalid primitive sequence received for the
current link state.
Were one or more event codes found?
YES NO
↓ Perform director fault isolation at the management server or
customer-supplied server running the EFCM Lite application.
Go to step 3.
Go to Ta ble 3- 3 on page 3-3 to interpret event codes.
MAP 0100: Power Distribution Analysis
This MAP describes fault isolation for the director power distribution
system, including defective AC power cords, redundant power
supplies, or the power module assembly.
1
Was an event code 200, 201, 202, or 208 observed at the Intrepid
6064 Event Log (management server) or at the SANpilot event log?
YES NO
↓ Go to step 10.