FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
3-36
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
Is a failure indicated?
YES NO
The director appears operational. Exit MAP.
5
Ensure the power supply is correctly installed and seated in the
director. If required, partially remove and reseat the power supply.
Was a corrective action performed?
YES NO
Go to step 7.
6
Verify redundant power supply operation.
a. Inspect the power supply and ensure the green PWR OK LED
illuminates and all amber LEDs extinguish.
b. At the management server Hardware View, observe the graphic
representing the power supply and ensure a failure symbol
(blinking red and yellow diamond) does not appear.
Is a failure indicated?
YES NO
The director appears operational. Exit MAP.
7
A redundant power supply failed and must be removed and replaced
(RRP: Power Supply on page 5-22).
This procedure is concurrent and can be performed while
director power is on.
Perform the data collection procedure as part of FRU removal
and replacement.
ATTENTION! Do not remove a power supply unless a replacement is
immediately available. To avoid director overheating, a power supply must
be replaced within five minutes.
Did power supply replacement solve the problem?
NO YES
The director appears operational. Exit MAP.