FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
MAP 0100: Power Distribution Analysis
3-37
Maintenance Analysis Procedures (MAPS)
Contact the next level of support. Exit MAP.
8
Power sense circuitry is defective in the indicated power supply or
there is a problem with facility input power.
Have the customer inspect and verify that facility power is within
specifications. These specifications are:
One single-phase connection for each power supply.
Input power between 100 and 240 VAC, and between
2 and 4 amps.
Input frequency between 47 and 63 Hz.
Is facility power within specifications?
NO YES
Go to step 7.
Ask the customer to correct the facility power problem. When facility
power is corrected, continue to the next step.
9
Verify director operation:
a. Inspect the director front bezel and ensure the green power LED
illuminates. Inspect the active CTP2 card and ensure the green
LED illuminates.
b. Inspect both power supplies. Ensure both green PWR OK LEDs
illuminate and all amber LEDs extinguish.
c. At the management server Hardware View, observe all graphics
representing FRUs and power supplies, and ensure emulated
green LEDs illuminate.
Is a failure indicated?
YES NO
The director appears operational. Exit MAP.
Contact the next level of support. Exit MAP.