FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
3-38
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
10
Is fault isolation being performed at the director?
YES NO
Fault isolation is being performed at the management server,
customer-supplied server, or SANpilot interface. Go to
step 21.
11
Verify the director is connected to facility power and is powered on.
a. Ensure AC power cords (PS0 and PS1) are connected to the
rear of the director and to facility power receptacles. If not,
connect the cords as directed by the customer.
b. Ensure associated facility circuit breakers are on. If not, ask the
customer set the circuit breakers on.
c. Ensure the AC power cords are not damaged. If damaged,
replace the cords.
d. Ensure the power switch (circuit breaker) at the rear of the
director is set to the ON (up) position.
Continue.
12
Inspect the director for indications of being powered on:
At the front bezel, an illuminated power LED (green) or system
error LED (amber).
An illuminated green LED on the active CTP2 card.
At least one green PWR OK LED illuminated on a power supply.
Audio emanations and airflow from cooling fans.
Does the director appear powered on?
YES NO
Go to step 14.