FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
3-40
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
YES NO
The director appears operational. Exit MAP.
17
Both power supplies failed and must be removed and replaced.
(RRP: Power Supply on page 5-22). Perform the data collection
procedure as part of FRU removal and replacement.
ATTENTION! Do not remove a power supply unless a replacement is
immediately available. To avoid director overheating, a power supply must
be replaced within five minutes.
Did dual power supply replacement solve the problem?
NO YES
The director appears operational. Exit MAP.
A dual power supply failure is not confirmed. Replace both original
power supplies. Continue.
18
A power module assembly failure is indicated and the FRU must be
removed and replaced (RRP: Power Module Assembly on
page 5-33). This procedure is nonconcurrent and must be performed
while director power is off.
Did power module assembly replacement solve the problem?
NO YES
The director appears operational. Exit MAP.
A power module assembly failure is not confirmed. Replace the
original power module assembly. Continue.
19
One or both power supplies appear operational, but logic cards are
not receiving DC power. In-card circuit breakers for all logic cards
may have tripped due to a power surge, or the backplane failed.
Power cycle the director to reset all logic cards (Power-On Procedure
on page 4-52).
Did power cycling the director solve the problem?
NO YES
The director appears operational. Exit MAP.