FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
MAP 0100: Power Distribution Analysis
3-41
Maintenance Analysis Procedures (MAPS)
20
The backplane failed and must be removed and replaced (RRP:
Backplane on page 5-36).
This procedure is nonconcurrent and must be performed while
director power is off.
Perform the data collection procedure as part of FRU removal
and replacement.
Did backplane replacement solve the problem?
NO YES
The director appears operational. Exit MAP.
Contact the next level of support. Exit MAP.
21
Is fault isolation being performed at the management server or
customer-supplied server?
YES NO
Fault isolation is being performed at the SANpilot interface.
Go to step 25.
22
At the Hardware View, does a yellow triangle appear at the alert panel
and a blinking red and yellow diamond (failed FRU indicator) appear
to overlay a power supply graphic?
NO YES
A redundant power supply failed. Go to step 7.
23
At the Hardware View, does a grey square appear at the alert panel, a
No Link status appear at the Intrepid 6064 Status table, and
graphical FRUs appear uninstalled?
YES NO
A green circle appears at the alert panel and the director
appears operational. Exit MAP.
The grey square indicates the management server or
customer-supplied server cannot communicate with the director
because:
The director-to-server Ethernet link failed.