MAP 0100: Power Distribution Analysis
3-41
Maintenance Analysis Procedures (MAPS)
20
The backplane failed and must be removed and replaced (RRP:
Backplane on page 5-36).
• This procedure is nonconcurrent and must be performed while
director power is off.
• Perform the data collection procedure as part of FRU removal
and replacement.
Did backplane replacement solve the problem?
NO YES
↓ The director appears operational. Exit MAP.
Contact the next level of support. Exit MAP.
21
Is fault isolation being performed at the management server or
customer-supplied server?
YES NO
↓ Fault isolation is being performed at the SANpilot interface.
Go to step 25.
22
At the Hardware View, does a yellow triangle appear at the alert panel
and a blinking red and yellow diamond (failed FRU indicator) appear
to overlay a power supply graphic?
NO YES
↓ A redundant power supply failed. Go to step 7.
23
At the Hardware View, does a grey square appear at the alert panel, a
No Link status appear at the Intrepid 6064 Status table, and
graphical FRUs appear uninstalled?
YES NO
↓ A green circle appears at the alert panel and the director
appears operational. Exit MAP.
The grey square indicates the management server or
customer-supplied server cannot communicate with the director
because:
• The director-to-server Ethernet link failed.