FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)
3
MAP 0100: Power Distribution Analysis
3-43
Maintenance Analysis Procedures (MAPS)
Continue.
27
Ensure the director reporting the problem is connected to facility AC
power and the power switch (circuit breaker) at the rear of the director
is set to the ON (up) position. Inspect the director for indications of
being powered on:
• At the front bezel, an illuminated power LED (green) or system
error LED (amber).
• An illuminated green LED on the active CTP2 card.
• At least one green PWR OK LED illuminated on a power supply.
• Audio emanations and airflow from cooling fans.
Does the director appear powered on?
YES NO
↓ Go to step 14.
Analysis for an Ethernet link or dual CTP2 card failure is not
described in this MAP. Go to MAP 0000: Start MAP on page 3-9. If
this is the second time at this step, contact the next level of support.
Exit MAP.
28
Inspect power supply operational states at the SANpilot interface.
a. At the View panel, click the FRU Properties tab. The View panel
(FRU Properties tab) displays.
b. Inspect the Status fields for both power supplies.
Does the Status field display a Failed message for either power
supply?
NO YES
↓ A redundant power supply failed. Go to step 7.
The director appears operational. Exit MAP.