FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
3-44
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
MAP 0200: POST Failure Analysis
When the director is powered on, it performs a series of power-on
self-tests (POSTs). When POSTs complete, the director performs an
initial program load (IPL) that loads firmware and brings the unit
online. This MAP describes fault isolation for problems that may
occur during the POST/IPL.
If an error is detected, the POST/IPL continues in an attempt to
initialize the director and bring it online. An event code 400 displays
when the director completes the POST/IPL.
1
Ensure the director reporting the problem is connected to facility AC
power and the power switch (circuit breaker) at the rear of the director
is set to the ON (up) position. Inspect the director for indications of
being powered on:
At the front bezel, an illuminated power LED (green) or system
error LED (amber).
An illuminated green LED on the active CTP2 card.
At least one green PWR OK LED illuminated on a power supply.
Audio emanations and airflow from cooling fans.
Does the director appear powered on?
YES NO
An AC power distribution problem is indicated, and analysis
for the failure is not described in this MAP. Go to MAP 0100:
Power Distribution Analysis on page 3-34. Exit MAP.
2
Was an event code 400, 411, or 413 observed at the Intrepid 6064
Event Log or at the SANpilot event log?
YES NO
Analysis for the failure is not described in this MAP. Go to
MAP 0000: Start MAP on page 3-9. Exit MAP.