FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
3-60
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
Does the director appear powered on?
YES NO
A power distribution problem is indicated. Go to MAP 0100:
Power Distribution Analysis on page 3-34. Exit MAP.
6
At the director, inspect the amber LED at the top of each CTP2 card.
Is the amber LED illuminated on both CTP2 cards?
NO YES
Failure of both CTP2 cards is indicated. Go to MAP 0500:
FRU Failure Analysis on page 3-75. Exit MAP.
7
The director-to-server Ethernet link failed. At the physical map, right-
click the icon with the grey square and exclamation mark representing
the director or switch reporting the problem. A pop-up menu appears.
Select the Element Manager option from the menu. The Element
Manager application opens and the Hardware View displays. At the
Hardware View:
A grey square appears at the alert panel.
No FRUs are visible for the director.
The Intrepid 6064 Status table is yellow, the Status field displays
No Link, and the Reason field displays an error message.
Tabl e 3-8 lists the error messages and associated steps that describe
fault isolation procedures.
Table 3-8 MAP 400: Error Messages
Error Message Action
Never connected. Go to step 8.
Link timeout. Go to step 8.
Protocol mismatch. Go to step 15.
Duplicate session. Go to step 18.
Unknown network address. Go to step 21.
Incorrect product type. Go to step 23.