FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

3
MAP 0500: FRU Failure Analysis
3-77
Maintenance Analysis Procedures (MAPS)
3
Is fault isolation being performed at the director?
YES NO
Fault isolation is being performed at the management server
or customer-supplied server, or SANpilot interface. Go to
step 10.
4
Inspect both fan modules at the rear of the director. Fan module LEDs
can be inspected through the hexagonal cooling vents of the radio
frequency interference (RFI) shield.
Does inspection of a director fan module indicate a failure? Indicators
include:
The amber LED is illuminated but not blinking (beaconing) on
one or both fan modules.
One or more cooling fans are not rotating.
YES NO
Go to step 6.
5
One or more cooling fans failed, and one or both fan modules must be
removed and replaced (RRP: Fan Module on page 5-30).
If a multiple fan failure caused a thermal shutdown, power on the
director after the fan modules are replaced (Power-On
Procedure on page 4-52).
811 Critically hot temperature warning (CTP2 card
thermal sensor).
Go to step 7.
812 CTP2 card shutdown due to thermal violation. Go to step 7.
850 System shutdown due to CTP2 card thermal
violations.
Go to step 7.
Table 3-9 MAP 500: Event Codes (continued)
Event
Code
Explanation Action