FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)
3
MAP 0500: FRU Failure Analysis
3-79
Maintenance Analysis Procedures (MAPS)
Is the amber LED on an SBAR assembly illuminated but not blinking
(beaconing)?
YES NO
↓ The director appears operational. Exit MAP.
9
An SBAR assembly failed and must be removed and replaced (RRP:
SBAR Assembly on page 5-26).
• This procedure is concurrent and can be performed while
director power is on.
• Perform the data collection procedure as part of FRU removal
and replacement.
Did SBAR assembly replacement solve the problem?
NO YES
↓ The director appears operational. Exit MAP.
Contact the next level of support. Exit MAP.
10
Is fault isolation being performed at the management server or
customer-supplied server?
YES NO
↓ Fault isolation is being performed at the SANpilot interface.
Go to step 18.
11
Does a blinking red and yellow diamond (failed FRU indicator) appear
to overlay a fan module graphic at the Hardware View?
NO YES
↓ A fan module failure is indicated. Go to step 5.
12
Does a blinking red and yellow diamond (failed FRU indicator) appear
to overlay a CTP2 card graphic at the Hardware View?
NO YES
↓ A CTP2 card failure is indicated. Go to step 7.