MAP 0600: Port Card Failure and Link Incident Analysis
3-101
Maintenance Analysis Procedures (MAPS)
Did the link incident recur?
YES NO
↓ The Fibre Channel link and director appear operational.
Exit MAP.
37
Disconnect the fiber-optic jumper cable from the director port and
connect the cable to a spare port.
Is a link incident reported at the new port?
YES NO
↓ Go to step 39.
38
The attached device is causing the recurrent link incident. Notify the
customer of the problem and have the system administrator:
a. Inspect and verify operation of the attached device.
b. Repair the attached device if a failure is indicated.
c. Monitor port operation for approximately five minutes.
Did the link incident recur?
YES NO
↓ The attached device, Fibre Channel link, and director appear
operational. Exit MAP.
Contact the next level of support. Exit MAP.
39
The director port reporting the problem is causing the recurrent link
incident. The recurring link incident indicates port or port card
degradation and a possible pending failure. Go to step 6.
40
A port card is not recognized by director firmware because the
firmware version is not supported or the port card failed. Advise the
customer of the problem and determine the correct firmware version
to download from the management server or customer-supplied
server.
Download the firmware (Download a Firmware Version to a Director
on page 4-64). Perform the data collection procedure after the
download.