FW 07.00.00/HAFM SW 08.06.00 McDATA Intrepid 6064 Director Installation and Service Manual (620-000108-920, April 2005)

5
RRP: SBAR Assembly
5-29
Removal and Replacement Procedures (RRPs)
7. At the management server or at a web browser connected to the
SANpilot interface, inspect the Event Log. Ensure the following
event codes appear in the log:
600 - SBAR card hot-insertion initiated.
601 - SBAR card hot-insertion completed.
If an event code 601 does not appear in the log, go to MAP 0000:
Start MAP on page 3-9 to isolate the problem.
8. Perform one of the following to verify SBAR operation:
If at the management server, open the Hardware View and
observe the SBAR graphic to ensure no alert symbols appear
that indicate a failure (yellow triangle or red diamond). If a
problem is indicated, go to MAP 0000: Start MAP on page 3-9
to isolate the problem.
If at a web browser connected to the SANpilot interface, open
the Switch tab at the View panel and ensure no amber LEDs
illuminate that indicate an SBAR failure. If a problem is
indicated, go to MAP 0000: Start MAP on page 3-9 to isolate
the problem.
9. Replace the RFI shield (RRP: RFI Shield on page 5-25).
10. Perform the data collection procedure (Collecting Maintenance
Data on page 4-39).
11. If the customer requests the replacement SBAR assembly be set as
the active SBAR, perform a FRU switchover. At the Hardware
View, right-click the graphic representing the replacement
assembly to open a pop-up menu, then select Switchover.
12. Perform one of the following to clear the system error (ERR) LED:
If at the management server, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from a
FRU) to open a menu.
b. Click the Clear System Error Light menu selection.
If at a web browser connected to the SANpilot interface:
a. Click the Switch tab at the Operations panel. The Operations
panel opens with the Switch page displayed.