FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Installation Guide (AA-RSNGD-TE, July 2004)

Installing and Configuring the Director
53Director 2/64 Installation Guide
Figure 14: Securing the rear angle brackets
7. Using a torque driver, torque the screws to 22 in/lb.
8. Connect the remaining ends of the PDU power cords to separate PDUs (if
installed), as shown in Figure 15; otherwise, connect the two standard AC
power cords.
Note: Hewlett-Packard recommends installing an optional PDU in the rack.
Hewlett-Packard ships two PDU power cords with the Director.
WARNING: Hewlett-Packard power cords are provided for each director
power supply. To prevent personal injury by electric shock, use only the
supplied power cords. Also, verify that the facility power receptacle is the
correct type, supplies the required voltage, and is properly grounded.
9. Connect the equipment rack power cords to separate (for redundancy) facility
power sources, providing single-phase, 120 to 240 VAC current.