FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Installation Guide (AA-RSNGD-TE, July 2004)

Installing and Configuring the Director
62 Director 2/64 Installation Guide
WARNING: The Director weighs approximately 115 pounds. Use proper
handling and lifting equipment to reduce the possibility of injury or product
damage.
1. Carefully position the switch in the front of the rack and onto the rail tray, and
slide the switch back on the rails until the front mounting brackets are against
the front rack columns. Figure 24 illustrates using a lifting jack to position the
switch.
Figure 24: Positioning the switch in the rack
2. Mount the switch in the rack, as shown in Figure 25:
a. On one side at the back of the switch, position an angle bracket (2) so
that the threaded holes (1) are against the slots (5) of the rear mounting
bracket and the angled side face out.
b. Insert the screws (6) through the rear mounting bracket slots into the
threaded nuts of the angle bracket.
c. Insert a second set of screws (4) through the angle bracket and the rail
column into the sheet metal nuts on the back rail (3).