FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)

Diagnostics
111Director 2/64 Service Manual
3
Is fault isolation being performed at the director?
YES NO
Fault isolation is being performed at the HAFM appliance or
Embedded Web Server interface. Go to step 10.
420 Backup CTP2 card NV-RAM failure. Go to step 7
426 Multiple ECC single-bit errors occurred. Go to step 7
433 Non-recoverable Ethernet fault. Go to step 7
440 Embedded port hardware failed. Go to step 7
604 SBAR assembly failure. Go to step 9
605 SBAR assembly revision not supported. Go to step 16
607 Director contains no operational SBAR
assemblies.
Go to step 9
805 High temperature warning (SBAR assembly
thermal sensor).
Go to step 9
806 Critically hot temperature warning (SBAR
assembly thermal sensor).
Go to step 9
807 SBAR assembly shutdown due to thermal
violation.
Go to step 9
810 High temperature warning (CTP2 card thermal
sensor).
Go to step 7
811 Critically hot temperature warning (CTP2 card
thermal sensor).
Go to step 7
812 CTP2 card shutdown due to thermal violation. Go to step 7
850 System shutdown due to CTP2 card thermal
violations.
Go to step 7
Table 11: MAP 0500: Event Codes (Continued)
Event Code Explanation Action