FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
Diagnostics
111Director 2/64 Service Manual
3
Is fault isolation being performed at the director?
YES NO
↓ Fault isolation is being performed at the HAFM appliance or
Embedded Web Server interface. Go to step 10.
420 Backup CTP2 card NV-RAM failure. Go to step 7
426 Multiple ECC single-bit errors occurred. Go to step 7
433 Non-recoverable Ethernet fault. Go to step 7
440 Embedded port hardware failed. Go to step 7
604 SBAR assembly failure. Go to step 9
605 SBAR assembly revision not supported. Go to step 16
607 Director contains no operational SBAR
assemblies.
Go to step 9
805 High temperature warning (SBAR assembly
thermal sensor).
Go to step 9
806 Critically hot temperature warning (SBAR
assembly thermal sensor).
Go to step 9
807 SBAR assembly shutdown due to thermal
violation.
Go to step 9
810 High temperature warning (CTP2 card thermal
sensor).
Go to step 7
811 Critically hot temperature warning (CTP2 card
thermal sensor).
Go to step 7
812 CTP2 card shutdown due to thermal violation. Go to step 7
850 System shutdown due to CTP2 card thermal
violations.
Go to step 7