FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
Diagnostics
113Director 2/64 Service Manual
6
Inspect the faceplates of both CTP2 cards at the front of the director.
Is the amber LED at the top of a CTP2 card illuminated but not blinking
(beaconing)?
YES NO
↓ Go to step 8.
7
A CTP2 card failed and must be removed and replaced (“RRP: Redundant CTP2
Card” on page 231).
■ This procedure is concurrent and can be performed while director power is on.
■ Perform the data collection procedure as part of FRU removal and
replacement.
Note: Do not remove and replace a CTP2 card if the backup CTP2 card is not fully
operational and director power is on. The director IP address, configuration data, and
other operating parameters will be lost.
Did CTP2 card replacement solve the problem?
NO YES
↓ The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
8
Inspect both SBAR assemblies at the rear of the director. SBAR assembly LEDs
can be inspected through the hexagonal cooling vents of the RFI shield.
Is the amber LED on an SBAR assembly illuminated but not blinking
(beaconing)?
YES NO
↓ The director is operational. Exit MAP.