FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
Repair Information
195Director 2/64 Service Manual
Channel Wrap Test (FICON)
A channel wrap test is a diagnostic procedure that checks FICON host-to-director
link connectivity by returning the output of the host as input. The test is host
initiated, and transmits ECHO extended link service (ELS) command frames to a
director port enabled for channel wrapping. The director port echoes the frames
back to the host.
To perform a channel wrap test for a director-attached host:
1. Notify the customer a disruptive channel wrap test will be performed on the
host-to-director FICON link.
2. Open the HAFM application. The View All - HAFM 8 main window displays.
a. Double-click the icon representing the director for which the channel
wrap test will be configured. The Hardware View for the selected director
displays.
b. At the Hardware View, verify the location of the port to be configured for
the channel wrap test. When the mouse pointer is passed over a graphical
UPM card on the front view of the director, the card highlights with a blue
border and a pop-up displays with the following information:
— Port card type (UPM).
— Chassis slot number (0 through 15 inclusive).
— The four consecutive port numbers on the selected card. Valid port
numbers are in the range of 0 through 63 inclusive.
c. Double-click the UPM card with the port to be configured. The Port Card
View for the selected card displays.
d. Right-click the port to be configured, then click Channel Wrap. The
Channel Wrap On for Port n (where n is the port number) window
displays.
e. Click OK to enable channel wrapping for the port.
3. Perform the Fibre Channel link test at the FICON host attached to the
configured port. For test instructions, refer to the service documentation
delivered with the FICON system.