FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
FRU Removal and Replacement
233Director 2/64 Service Manual
b. Insert the torque tool(1) into the cam Allen screw at the top of the
card(2). To unseat the CTP2 card and cam it out of the backplane, turn
the screw counterclockwise until the tool turns freely, as shown in
Figure 74.
Figure 74: CTP2 card removal and replacement
6. Pull the CTP2 card from its card track and remove it from the director chassis.
Place the card in an antistatic bag to provide ESD protection.
Replacing a Redundant CTP2 card
To replace a redundant CTP2 card:
1. Wait approximately 20 seconds after removal of the failed CTP2 card to begin
this replacement procedure.
2. Remove the replacement card from its protective antistatic bag.
3. Hold the card by its stiffener and insert it in the chassis card track, as shown in
Figure 74. The label identifying the card should be at the top. Verify the card
is aligned in the card tracks, then slide it forward until it makes contact with
the backplane.
SHR-2286
StorageWorks SAN
6064
1
2