FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
FRU Removal and Replacement
236 Director 2/64 Service Manual
— If at an EWS interface:
a. Click the Switch tab at the Operations panel. The Operations panel
displays with the Switch page open.
b. Click the Sys Err Light tab. The Switch page displays with the Sys
Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
16. If necessary, close and lock the equipment cabinet door.
RRP: UPM Card
Use the following procedures to remove or replace a UPM card. A list of tools
required is provided.
Tools Required
The following tools are required to perform these procedures.
■ ESD grounding cable and wrist strap.
■ Torque tool and hex adapter (provided with the director).
■ Fiber optic protective plugs (provided with the director).
■ Protective caps (provided with fiber optic jumper cables).
■ Fiber optic cleaning kit.
Removing a UPM Card
To remove a UPM card:
1. Notify the customer that all ports on the defective UPM card will be blocked.
Ensure the customer’s system administrator quiesces Fibre Channel frame
traffic through any operational ports on the card and sets attached devices
offline.
2. If the director is installed in a stand-alone configuration, go to step 3. If the
director is rack-mounted, unlock and open the cabinet front door as directed
by the customer representative.