8. At the Hardware View, click Logs > Event Log. The Event Log displays.
Ensure the following event codes display in the log:
500—Port card hot-insertion initiated.
501—Port card has been recognized.
If an event code 501 does not display in the log, go to “MAP 0000: Start
MAP” on page 46 to isolate the problem.
9. At the Hardware View, double-click the graphic representing the replacement
card to open the Port Card View. At the Port Card View:
a. Ensure no alert symbols display that indicate a failure (yellow triangle or
red diamond).
b. Verify that UPM card information (FRU name, position, and state) is
correct.
If a problem is indicated, go to “MAP 0000: Start MAP” on page 46 to isolate
the problem.
10. Restore communication to the replacement UPM card and set the card online
as directed by the customer (“Unblock a UPM Card” on page 209). Inform the
customer the UPM card is available for use.
11. Perform the data collection procedure (
Collecting Maintenance Data” on
page 197
).
12. Perform one of the following to clear the system error (ERR) LED:
If at the HAFM application, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from an FRU) to open
a menu.
b. Click Clear System Error Light.
If at an EWS interface:
a. Click the Switch tab at the Operations panel. The Operations panel
displays with the Switch page open.
b. Click the Sys Err Light tab. The Switch page displays with the Sys
Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
13. If necessary, close and lock the equipment cabinet door.