FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
FRU Removal and Replacement
243Director 2/64 Service Manual
5. Inspect the UPM card with the replacement port transceiver to ensure all
amber LEDs are extinguished. If any amber LEDs are illuminated, go to
“MAP 0000: Start MAP” on page 46 to isolate the problem.
6. At the Hardware View, click Logs > Event Log. The Event Log displays.
Ensure an event code 510 (SFP optics card hot-insertion initiated) displays in
the log.
If an event code 510 does not display in the log, go to “MAP 0000: Start
MAP” on page 46 to isolate the problem.
7. Perform one of the following to verify UPM card operation:
— At the Hardware View, observe the graphic representing the replacement
card and ensure no alert symbols display that indicate a failure (yellow
triangle or red diamond). If a problem is indicated, go to “MAP 0000:
Start MAP” on page 46 to isolate the problem.
— At the EWS interface, open the Switch tab at the View panel and ensure
no amber LEDs illuminate that indicate a UPM card failure. If a problem
is indicated, go to “MAP 0000: Start MAP” on page 46 to isolate the
problem.
8. Restore communication to the port with the replacement transceiver as
directed by the customer (“Unblock a Port” on page 209). Inform the customer
the port is available for use.
9. Perform one of the following to clear the system error (ERR) LED:
— If at the HAFM application, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from an FRU) to open
a menu.
b. Click Clear System Error Light.
— If at an EWS interface:
a. Click the Switch tab at the Operations panel. The Operations panel
displays with the Switch page open.
b. Click the Sys Err Light tab. The Switch page displays with the Sys
Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
10. If necessary, close and lock the equipment cabinet door.