FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
FRU Removal and Replacement
245Director 2/64 Service Manual
Replacing a UPM Filler Blank
To replace a filler blank:
1. Remove the filler blank from its packaging.
2. Hold the filler blank by its stiffener and insert it in the chassis card track, as
shown in Figure 77.
3. To secure the filler blank, sequentially insert the torque tool into each locking
Allen screw. Turn each screw clockwise until you feel the torque tool release
and hear a clicking sound. As each screw turns clockwise, the filler blank
locks into place.
4. Verify the filler blank stiffener is flush with the front of the card cage and is
even with other director logic cards.
5. If necessary, close and lock the equipment cabinet door.
RRP: Redundant Power Supply
Use the following procedures to remove or replace a redundant power supply. A
list of tools required is provided.
Tools Required
The ESD grounding cable and wrist strap are required to perform these
procedures.
Removing a Redundant Power Supply
To remove a redundant power supply:
1. If the director is installed in a stand-alone configuration, go to step 2. If the
director is rack-mounted, unlock and open the cabinet front door as directed
by the customer representative.
2. Follow ESD procedures by attaching a wrist strap to the director chassis and
your wrist, as shown in Figure 72 on page 229.
Caution: To avoid causing machine errors or damage while working on the
director, follow ESD procedures by connecting a grounding cable to the
director chassis and wearing an ESD wrist strap.