FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
FRU Removal and Replacement
248 Director 2/64 Service Manual
— If at an EWS interface:
a. Click the Switch tab at the Operations panel. The Operations panel
displays with the Switch page open.
b. Click the Sys Err Light tab. The Switch page displays with the Sys
Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
11. If necessary, close and lock the equipment cabinet door.
RRP: Redundant SBAR Assembly
Use the following procedures to remove or replace a redundant SBAR assembly
(two assemblies in the director) with the backup SBAR assembly operational. A list of
tools required is provided.
Tools Required
The following tools are required to perform these procedures.
■ Standard flat-tip screwdriver.
■ ESD grounding cable and wrist strap.
■ Torque tool and hex adapter (provided with the director).
Removing a Redundant SBAR Assembly
To remove a redundant SBAR assembly:
1. If the director is installed in a stand-alone configuration, go to step 2. If the
director is rack-mounted, unlock and open the cabinet rear door as directed by
the customer representative.
2. Follow ESD procedures by attaching a wrist strap to the director chassis and
your wrist, as shown in Figure 73 on page 230.
Caution: To avoid causing machine errors or damage while working on the
director, follow ESD procedures by connecting a grounding cable to the
director chassis and wearing an ESD wrist strap.
3. Remove the RFI shield.