FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
FRU Removal and Replacement
251Director 2/64 Service Manual
8. Perform one of the following to verify SBAR operation:
— At the Hardware View, observe the graphic representing the replacement
card and ensure no alert symbols display that indicate a failure (yellow
triangle or red diamond). If a problem is indicated, go to “MAP 0000:
Start MAP” on page 46 to isolate the problem.
— At the EWS interface, open the Switch tab at the View panel and ensure
no amber LEDs illuminate that indicate a SBAR failure. If a problem is
indicated, go to “MAP 0000: Start MAP” on page 46 to isolate the
problem.
9. At the Hardware View, double-click the graphic representing the replacement
SBAR assembly to open the FRU Properties dialog box. Verify that
information (FRU name, position, and state) is correct. If a problem is
indicated, go to “MAP 0000: Start MAP” on page 46 to isolate the problem.
10. Replace the RFI shield.
11. Perform the data collection procedure (
“Collecting Maintenance Data” on
page 197
).
12. If the customer requests the replacement SBAR assembly be set as the active
SBAR, perform an FRU switchover. At the Hardware View, right-click the
graphic representing the replacement assembly to open a menu, then click
Switchover.
13. Perform one of the following to clear the system error (ERR) LED:
— If at the HAFM application, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from an FRU) to open
a menu.
b. Click Clear System Error Light.
— If at an EWS interface:
a. Click the Switch tab at the Operations panel. The Operations panel
displays with the Switch page open.
b. Click the Sys Err Light tab. The Switch page displays with the Sys
Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
14. If necessary, close and lock the equipment cabinet door.