FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
FRU Removal and Replacement
263Director 2/64 Service Manual
13. At the Hardware View, observe all FRU graphics and ensure no alert symbols
display that indicate a failure (yellow triangle or red diamond). If a problem is
indicated, go to “MAP 0000: Start MAP” on page 46 to isolate the problem.
14. Perform the data collection procedure (
“Collecting Maintenance Data” on
page 197
).
15. Perform one of the following to clear the system error (ERR) LED:
— If at the HAFM application, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from an FRU) to open
a menu.
b. Click Clear System Error Light.
— If at an EWS interface:
a. Click the Switch tab at the Operations panel. The Operations panel
displays with the Switch page open.
b. Click the Sys Err Light tab. The Switch page displays with the Sys
Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
16. If necessary, close and lock the equipment cabinet door.