FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)

Diagnostics
60 Director 2/64 Service Manual
28
Is the power LED (green) at the director front bezel illuminated?
NO YES
Go to step 30.
A faulty power LED is indicated, but director and Fibre Channel port operation is
not disrupted. The LED is connected to the circuitry in a fan module, and the
module must be removed and replaced (“RRP: Redundant Fan Module” on
page 252). Exit MAP.
29
Inspect the director for indications of being powered on, such as:
At the front bezel, an illuminated power LED (green) or system error LED
(amber).
An illuminated green LED on the active CTP2 card, and illuminated green
PWR OK LEDs on both power supplies.
Audio emanations and airflow from cooling fans.
Is the director powered on?
YES NO
A power distribution problem is indicated. Go to step 23 to obtain
event codes. If no event codes are found, go to “MAP 0100: Power
Distribution Analysis” on page 71. Exit MAP.
A faulty power LED is indicated, but director and Fibre Channel port operation is
not disrupted. The LED is connected to the circuitry in a fan module, and the
module must be removed and replaced (“RRP: Redundant Fan Module” on
page 252). Exit MAP.
30
Is the system error LED (amber) at the director front bezel blinking?
YES NO
Go to step 32.