FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)

Diagnostics
61Director 2/64 Service Manual
31
Unit beaconing is enabled for the director.
1. Consult the customer and next level of support to determine the reason unit
beaconing is enabled.
2. Disable unit beaconing.
a. At the Hardware View, right-click the front bezel graphic (away from an
FRU). A menu displays.
b. Click Enable Unit Beaconing. The check mark disappears from the box
adjacent to the option, and unit beaconing is disabled.
Was unit beaconing enabled because a director failure or degradation was
suspected?
YES NO
The director is operational. Exit MAP.
Go to step 24.
32
Is the system error LED (amber) at the director front bezel illuminated?
YES NO
The director is operational. Verify operation at the HAFM appliance.
Go to step 3.
33
Check FRUs (UPM cards, CTP2 cards, SBAR assemblies, power supplies, and fan
modules) for failure symptoms.
Is the amber LED at the top of a UPM card illuminated or are any amber LEDs
associated with Fibre Channel ports illuminated?
NO YES
A UPM card or Fibre Channel port failure is indicated. Go to step 23
to obtain event codes. If no event codes are found, go to “MAP 0600:
UPM Card Failure and Link Incident Analysis” on page 118.
Exit MAP.