FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)

Diagnostics
74 Director 2/64 Service Manual
Did power supply replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
8
Power sense circuitry is defective in the indicated power supply or there is a
problem with facility input power.
Have the customer inspect and verify that facility power is within specifications.
These specifications are:
One single-phase connection for each power supply.
Input power between 100 and 240 VAC, and between 2 and 4 amps.
Input frequency between 47 and 63 Hz.
Is facility power within specifications?
NO YES
Go to step 7.
Ask the customer to correct the facility power problem. When facility power is
corrected. Continue.
9
Verify director operation:
1. Inspect the director front bezel and ensure the green power LED illuminates.
Inspect the active CTP2 card and ensure the green LED illuminates.
2. Inspect both power supplies. Ensure both green PWR OK LEDs illuminate
and all amber LEDs extinguish.
3. At the Hardware View, observe all graphics representing FRUs and power
supplies, and ensure emulated green LEDs illuminate.
Is a failure indicated?
YES NO
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.