FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)

Diagnostics
78 Director 2/64 Service Manual
20
The backplane failed and must be removed and replaced (“RRP: Backplane” on
page 258).
This procedure is non-concurrent and must be performed while director power
is off.
Perform the data collection procedure as part of FRU removal and
replacement.
Did backplane replacement solve the problem?
NO YES
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
21
Is fault isolation being performed at the HAFM appliance?
YES NO
Fault isolation is being performed at the Embedded Web Server
interface. Go to step 25.
22
At the Hardware View, does a yellow triangle display at the alert panel and a
blinking red and yellow diamond (failed FRU indicator) display over a power
supply graphic?
NO YES
A redundant power supply failed. Go to step 7.
23
At the Hardware View, does a grey square display at the alert panel, a No Link
status displays at the director Status table, and graphical FRUs are uninstalled?
YES NO
A green circle displays at the alert panel and the director is
operational. Exit MAP.