FW V06.XX/HAFM SW V08.02.00 HP StorageWorks Director 2/64 Service Manual (AA-RS2ED-TE, July 2004)
Diagnostics
83Director 2/64 Service Manual
5
The backplane failed POSTs (indicated by a 01 FRU code) and must be removed
and replaced (“RRP: Backplane” on page 258).
■ This procedure is non-concurrent and must be performed while director power
is off.
■ Perform the data collection procedure as part of FRU removal and
replacement.
Did backplane replacement solve the problem?
NO YES
↓ The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
6
A CTP2 card failed POSTs (indicated by a 02 FRU code) and must be removed
and replaced (“RRP: Redundant CTP2 Card” on page 231).
■ This procedure is concurrent and can be performed while director power is on.
■ Perform the data collection procedure as part of FRU removal and
replacement.
Note: Do not remove and replace a redundant CTP2 card if the backup CTP2 card is
not fully operational and director power is on. The director IP address, configuration
data, and other operating parameters will be lost.
05 Fan module. Go to step 8
06 Power supply. Go to step 9
08-0F UPM card. Go to step 10
Table 8: Byte 0 FRU Codes
Byte 0 Failed FRU Action