HP StorageWorks director 2/64 Order and Configuration Guide

HP Storageworks Direc
HP Storageworks DirecHP Storageworks Direc
or 2/64 in
tor 2/64 in tor 2/64 in
Rack With Laptop and Hub
Rack With Laptop and HubRack With Laptop and Hub
hp Storageworks 7
Racking the Director 2/64: The following HP racks are available for factory integration of
products and peripherals that are ordered with the factory integration product option ("Z"):
A4900A HP9000 Std Rack System E25 19" standard 25 EIA rack for servers and peripherals.
1.25 Meter rack.
A4901A HP9000 Std Rack System E33 19" standard 33 EIA rack for servers and
peripherals. 1.6 Meter rack.
A4902A HP9000 Std Rack System E41 19" standard 41 EIA rack for servers and
peripherals. 2.0 Meter rack.
Note: Also compatible with Standard Rittal 19” rack
The 2.0-meter rack supports 41U and a maximum weight of 2000 lbs. The Director 2/64 (9U) with
cable management (1Urack mount tray) is 10U high and each switch weighs ~115 lbs. Therefore, the
2.0 meter rack will support three Director 2/64’s Per Rack (w/ Hub and HAFM OmniBook kit, see
image below) or four Director 2/64’s (w/o Hub and HAFM OmniBook kit) with 1U to spare.
HP Storageworks Directtor 2/64 in
Rack With Laptop and Hub
HP Hub
HP Stora
g
eWorks
Director 2/64
HP Stora
g
eWorks
HAFM Server
Other Racking accessories:
302659-B21 Director rack mounting
kit (9000 and millennium cabinets)
254520-B21 Director rack mounting
kit (M-Series cabinets)
Plan for AC power:
Plan for facility power sources for each
equipment rack. Directors in a rack
operate at 50 to 60 Hertz (Hz) and
100 to 240 volts alternating current
(VAC), and require a minimum
dedicated 5-ampere service. If two
power sources are supplied (optional
but recommended for high
availability), the equipment rack
contains two customer-specified
external power cords. Each cord
should be connected to a separate
power circuit, or both should be connected to an uninterruptible power supply (UPS). Several types of
power cables and plugs are available to meet local electrical requirements.
HP Stora
g
eWorks
Director 2/64
Director 2/64 Airflow:
Airflow enters in the FRONT of the director, is pulled UP and exits out the SIDES. Cooling airflow clearances:
Right and left side: 5.1 centimeters (2.0 inches), Front and rear: 7.6 centimeters (3.0 inches)
Configuration Guide hp StorageWorks Director 2/64